H648 HART Temperature module
APPLICATION
Used for RTD, TC, Ohm, mV
SPECIFICATIONS
Power supply: 9-32VDC
Output: 4~20mA with HART (2-wire)
Stability:
0.01°C(RTD), 0.1°C(E J K N T), 0.2°C(B R S)
Accuracy:
0.1°C(RTD), 0.5°C(E J K N T), 1.0°C(B R S)
Operating temperature:-40°C ~ +85°C
Dimension:
H648:Φ= 44mm, Mounting hole pitch D = 33mm
H3051WD:Φ= 62mm, Mounting hole D = 55mm
H649: DIN rail mounting
Used for RTD, TC, Ohm, mV
SPECIFICATIONS
Power supply: 9-32VDC
Output: 4~20mA with HART (2-wire)
Stability:
0.01°C(RTD), 0.1°C(E J K N T), 0.2°C(B R S)
Accuracy:
0.1°C(RTD), 0.5°C(E J K N T), 1.0°C(B R S)
Operating temperature:-40°C ~ +85°C
Dimension:
H648:Φ= 44mm, Mounting hole pitch D = 33mm
H3051WD:Φ= 62mm, Mounting hole D = 55mm
H649: DIN rail mounting
FEATURES
Ø High-voltage isolation: As high as 1000V for the isolation voltage between metal capacitance sensor processing circuit and main circuit.
Ø High reliability:Built-in multi-level protection circuit for high reliability. Outstanding EMC performance.
Ø H3051 LCD display: 360o rotation LCD display. More than one variable displayed on the LCD with backlight for dark environment.
Ø H649: DIN rail mounting and can be built completely independent 2-channel temperature modules.
Ø P3051WD(optional) : P3051WD replaces the HART protocol products of H3051WD with PROFIBUS-PA protocol and has the same dimensions with H3051WD. It can be connected to the Siemens S7 system.